![Smartgen HSC960 User Manual Download Page 32](http://html1.mh-extra.com/html/smartgen/hsc960/hsc960_user-manual_1297545032.webp)
HSC960 Genset Controller User Manual
HSC960 Genset Controller Version:1.0 2015-05-21 Page 32 of 37
10
COMMISSIONING
Please make the under procedures checking before commissioning,
——
Ensure all the connections are correct and wires diameter is suitable.
——
Ensure that the controller DC power has fuse, controller„s positive and negative connected to
start battery are correct.
——
Take proper action to prevent engine to crank disconnect (e. g. Remove the connection wire of
fuel valve). If checking is OK, make the start battery power on; choose manual mode and
controller will executive routine.
——
Set controller under manual mode, press “start” button, genset will start. After the setting times
as setting, controller will send signal of Start Fail; then press “stop” to reset controller.
——
Recover the action of stop engine start (e. g. Connect wire of fuel valve), press start button again,
genset will start. If everything goes well, genset will normal run after idle running (if idle run be
set). During this time, please watch for engine‟s running situations and AC generator‟s voltage
and frequency. If abnormal, stop genset running and check all wires connection according to this
manual.
——
Select the AUTO mode from controller‟s panel, connect remote start signal. genset will be started
automatically and into normal running, then controller send signal to close generator.
——
Cut-off remote start signal, the genset will be stopped automatically and the Open Generator
signal will be send out. If not like this, please check ATS‟ wires connection of control part
according to this manual.
——
If there is any other
question, please contact Smartgen‟s service.
11
TYPICAL APPLICATION
Figure 4-
Typical Application Diagram