HMU8-860 ATS Remote Monitoring Controller User Manual Page 29 of 50
No.
Item
Range
Default
Description
9
Duration
(0~30000)min
30
The duration time of genset running.
10
Scheduled Not Run
(0~1)
0
0: Disable 1: Enable
11
Cycle Selection
(0~2)
0
0: Monthly;
1: Weekly;
2: Daily.
12
Not Run Time
(Month)
(1~12)month
monthly
Jan.
Feb.
Mar.
Apr.
May
June
July
Aug.
Sep.
Oct.
Nov.
Dec.
13
Not Run Time
(Date)
(1~31)
1
The date of genset not start monthly.
14
Not Run Time
(Week)
Mon ~ Sun
Sunday
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
15
Not Run Time
(Hour)
(0~23)h
0
The time of genset not start.
16
Not Run Time
(Minute)
(0~59)min
0
17
Not Run Duration
(0~30000)min
30
The duration time of genset
NOT
running.
Load Setting
1
Elevator Enable
(0~1)
0
0: Disable 1: Enable
1
Elevator Delay
(0~300)s
300
It’s the delay time before the load
disconnect or switch transfer. Used for
control the running elevator stop at the
nearest floor until the switch transfer is
terminated.