background image

                         

 

HMU8-860 ATS Remote Monitoring Controller User Manual                                                  Page 39 of 50 

No. 

Item 

Description 

6

 

 

Gen2 Fault Input 

In  cycle  start,  if  the  input  is  active,  S2  Gens  start  will  be 
inhibited. 

7

 

 

Start Inhibit Input 

In  Auto  mode,  start  signal  will  be  deactivated  after  the  stop 
delay  has  expired.  In  Manual  mode,  if  the  genset  is  running, 
users should stop it manually; then the manual start signal will 
be deactivated.   

8

 

 

S1 Breaker Trip 

S1 breaker trip fault input. 

9

 

 

S2 Breaker Trip 

S2 breaker trip fault input. 

10

 

 

S1 Load Inhibit 

In  Manual  mode,  S1  manual  close  is  inhibited;  if  breaker  is 
already closed, users should open it manually. In Auto mode, if 
breaker is already closed, then load will disconnect or S2 takes 
load. 

11

 

 

S2 Load Inhibit 

In  Manual  mode,  S2  manual  close  is  inhibited;  if  breaker  is 
already closed, users should open it manually. In Auto mode, if 
breaker is already closed, then load will disconnect or S1 takes 
load. 

12

 

 

QS1 Ready PF 

When S1 close ready signal inputs, it needs to wait S1 PF input 
active before closing. 

13

 

 

QS2 Ready PF 

When S2 close ready signal inputs, it needs to wait S2 PF input 
active before closing. 

14

 

 

S1 Close Key Input   

Same as S1 close key, the self-reset key is used to control S1 
close. 

15

 

 

S2 Close Key Input   

Same as S2 close key, the self-reset key is used to control S2 
close. 

16

 

 

Open Input 

Same as open key, the self-reset key is used to control breaker 
open. 

17

 

 

Alarm Reset 

Reset the current alarm. 

18

 

 

Alarm Mute 

Silence the audible alarm. 

19

 

 

Manual NEL Trip Input 

Please select self-reset key to manually control NEL offload. 

20

 

 

Manual  NEL  Re-connect 
Input 

Please  select  self-reset  key  to  manually  control  NEL  on-load 
again. 

21

 

 

S1 Master Input 

Set S1 master use compulsively. 

22

 

 

S2 Master Input 

Set S2 master use compulsively. 

23

 

 

Forced Manual Mode 

Set the controller in Manual mode compulsively. 

24

 

 

Forced Auto Mode 

Set the controller in Auto mode compulsively. 

25

 

 

Panel Lock 

Panel key operations are inhibited (Except Up, Down, Confirm, 
Return and Alarm Reset and Alarm Mute keys). 

26

 

 

Reserved 

 

27

 

 

Scheduled 

Start/Stop 

Inhibit 

Schedule start and stop function are deactivated. 

28

 

 

Simulate S1 OK 

Simulate S1 voltage is normal; the S1 voltage abnormal delay 
is deactivated. 

29

 

 

Simulate S2 OK 

Simulate S2 voltage is normal; the S2 voltage abnormal delay 
is deactivated. 

Summary of Contents for HMU8-860

Page 1: ...HMU8 860 ATS REMOTE MONITORING CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Page 2: ...ncluding photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reprodu...

Page 3: ...struction NOTE Highlights an essential element of a procedure to ensure correctness CAUTION Indicates a procedure or practice which if not strictly observed could result in damage or destruction of eq...

Page 4: ...R CONFIGURATION OF MONITORING MODULE 20 4 3 2 PARAMETER CONFIGURATION OF MASTER CONTROL MODULE 20 4 3 3 ADVANCED PARAMETER CONFIGURATION 21 5 WIRING 22 5 1 HUM8 860 MONIROTING MODULE REAR PANEL 22 5 2...

Page 5: ...ller adopts high performance ARM chip large high resolution capacitive touch screen with Chinese and English display which can realize remote control data monitoring and parameter configuration of HAT...

Page 6: ...and power factor of master control module Display S1 S2 accumulated active energy reactive energy close times auto transfer times mains failure transfer times of master control module Display current...

Page 7: ...s 250m using Belden 9841 cable or equivalent Vibration Frequency 5Hz 8Hz Amplitude 7 5mm Range 8Hz 500Hz Fixed acceleration 2g IEC60068 2 6 Shock Acceleration 50g Pulse continuous time 11ms Waveform h...

Page 8: ...iption Alarm Warning alarm slow flash 1 time per second Shutdown alarm fast flash 5 times per second No alarm extinguish Comm It is always illuminated when the communication between display module and...

Page 9: ...ay Area Description Custom Description Character 1 Display HAT860 custome description character 1 Custom Description Character 2 Display HAT860 custome description character 2 Alarm Information Displa...

Page 10: ...n manual mode press it can control ATS to open QS2 Close When the master control module is in manual mode press it can control QS2 to close Manual Mode Press it to transfer master control module to ma...

Page 11: ...ts genset icon is shown in green and text indicates Genset Working when genset is in standby the icon is shown in gray and text indicates Genset Standby Fig 3 Genset Operation Interface Table 7 Key De...

Page 12: ...with master control configuration each page can display up to 6 items and the maximum number of items is 24 Fig 4 Manual Operation Interface of Load Stepwise Switch Table 8 Key Description of Load St...

Page 13: ...etailed Information Display Interface The detailed information interface displays S1 electric parameters includes phase voltage line voltage current phase sequence frequency information S2 electric pa...

Page 14: ...e overcurrent action is set as trip and S1 takes load current is greater than the set value 6 S2 Load Overcurrent Trip When the overcurrent action is set as trip and S2 takes load current is greater t...

Page 15: ...than the set value 2 S2 Load Overcurrent Overcurrent action is set as warning when S2 takes load current is greater than the set value 3 Forced Open Forced open non fire cutoff action is set as warni...

Page 16: ...event records including the serial number total numbers of the current event the type of event the detailed contents of the event and the time when it happened By and keys up to 200 event records can...

Page 17: ...output QS1 open output QS2 open output QS1 synchronous close QS2 synchronous close NEL1 trip NEL2 trip NEL3 trip Genset start S1 genset start S2 genset start Genset stop S1 genset stop S2 genset stop...

Page 18: ...fault alarm S1 genset fault S2 genset fault S1 breaker trip alarm S2 breaker trip alarm Input 1 6 comm Failure fault Output 1 3 comm Failure fault Load switching failure Earth fault QTIE close failure...

Page 19: ...this key to set the time and date of master control module Brightness Press this key to adjust the screen brightness of monitoring module adjusting range is 0 10 default is 6 and conduct lamp test ope...

Page 20: ...as follows 1 Select parameters to be configured by the tree diagram 2 Set parameters to be changed in the right window Press the numeric keypad key when necessary to pop up the numeric keypad 3 After...

Page 21: ...ation if communication fails and then returns to normal the monitoring module will re read and load the parameter configuration of the master control module NOTE3 The monitoring module cannot configur...

Page 22: ...nd is grounded Short connect terminal 4 and 6 and connect 120 terminal resistor 5 CAN L 0 5mm2 6 CAN H 0 5mm2 7 PE1 Protective earth 8 RS485 1 Terminal match resistor 120 0 5mm2 Used for connecting ma...

Page 23: ...sted shielding wire with 120 impedance whose single end is grounded Short connect terminal 20 and 22 and connect 120 terminal resistor 21 B 0 5mm2 22 A 0 5mm2 23 PE5 Protective earth NOTE1 Slave USB i...

Page 24: ...Parity 4 Stop Bit 1 2 2 1 1 Bit 2 2 Bits RS485 2 Setting Reserved 1 Module Address 1 254 001 The module address of current RS485 interface is not used when communicating with the master control modul...

Page 25: ...25 3 Subnet Mask 255 255 255 000 4 Gateway 192 168 010 001 5 DNS Address 211 138 024 066 6 2 PARAMETER CONTENTS AND SCOPES OF MASTER CONTROL MODULE Table 17 Parameter Contents and Scopes No Item Range...

Page 26: ...e it is abnormal if the value has fallen below the set value 17 Return Value 0 200 85 Lower limit return value of voltage it is normal only when the value has exceeded the set value 18 Rated Frequency...

Page 27: ...ain Open Delay 0 20 0 s 0 0 When the breaker fails to close for the first time then the module will open for the second time and the Again Open Delay begins after the delay has expired if it still fai...

Page 28: ...gen voltage lasts abnormal after the delay has expired genset fault alarm will be initiated Scheduled Run Not Run Setting 1 Schedule Run 0 1 0 0 Disable 1 Enable 2 Run Mode 0 1 0 0 Off Load 1 On Load...

Page 29: ...me Date 1 31 1 The date of genset not start monthly 14 Not Run Time Week Mon Sun Sunday Sunday Monday Tuesday Wednesday Thursday Friday Saturday 15 Not Run Time Hour 0 23 h 0 The time of genset not st...

Page 30: ...er than the set value and delay is over it will take off load 16 NEL Over Power Trip 1 Delay 0 3600 s 5 17 NEL Over Power Trip 2 Set Value 0 200 100 When load power is greater than the set value and d...

Page 31: ...o activate 11 Digital Input 6 0 159 0 Not Used 12 Active Type 0 1 0 0 Close to activate 1 Open to activate 13 Digital Input 7 0 159 0 Not Used 14 Active Type 0 1 0 0 Close to activate 1 Open to activa...

Page 32: ...0 0 Output NO 1 Output NC 12 Contents Setting 0 159 0 Not Used 13 Relay Output 7 Active Type 0 1 0 0 Output NO 1 Output NC 14 Contents Setting 0 159 0 Not Used 15 Relay Output 8 Active Type 0 1 1 0 O...

Page 33: ...36 Combined 2 or Out 2 Contents 0 159 0 Not Used 37 Combined 2 and Out Active Type 0 1 0 0 Output NO 1 Output NC 38 Combined 2 and Out Contents 0 159 0 Not Used 39 Combined 3 or Out 1 Active Type 0 1...

Page 34: ...ntents 0 159 0 Not Used 59 Combined 6 or Out 2 Active Type 0 1 0 0 Output NO 1 Output NC 60 Combined 6 or Out 2 Contents Setting 0 159 0 Not Used 61 Combined 6 and Out Active Type 0 1 0 0 Output NO 1...

Page 35: ...s parameter of monitoring module and master control mosule can be set simultaneously without affecting following communication 8 RS485 2 Baud Rate 0 3 2 0 2400bps 1 4800bps 2 9600bps 3 19200bps 9 RS48...

Page 36: ...nd switch according to set priority Enable This load breaker can be allowed to control c o when it is in working position 5 Fixed C O Time 0 1 0 0 Disable 1 Enable Disable Output time is detected acco...

Page 37: ...When the main breaker is manually closed opened prompt box Confirm to stepwise switch load will be popped out Press Up Down key to select Confirm Cancel then press Set key to confirm operation and ex...

Page 38: ...Line Volt Amplitude Difference Multiple 0 1 00 0 20 It is the multiple that line voltage amplitude difference set value of PT break judgment accounts for rated voltage 6 Break Reset Volt Multiple 0 1...

Page 39: ...lose ready signal inputs it needs to wait S2 PF input active before closing 14 S1 Close Key Input Same as S1 close key the self reset key is used to control S1 close 15 S2 Close Key Input Same as S2 c...

Page 40: ...1 Closed Input QS1 Closed feedback input 43 S2 Closed Input QS2 Closed feedback input 44 Reserved 45 Reserved 46 Reserved 47 Reserved 48 Reserved 49 Reserved 50 Reserved 51 Reserved 52 Load 1 Close St...

Page 41: ...r 8 closed status input 81 Load 8 Work Position Status Load breaker 8 work position status input 82 Load 8 Test Position Status Load breaker 8 test position status input 83 Load 8 Breaker Trip Load br...

Page 42: ...input 112 Load 16 Close Status Load breaker 16 closed status input 113 Load 16 Work Position Status Load breaker 16 work position status input 114 Load 16 Test Position Status Load breaker 16 test po...

Page 43: ...input 139 Load 22 Breaker Trip Load breaker 22 trip fault input 140 Load 23 Close Status Load breaker 23 closed status input 141 Load 23 Work Position Status Load breaker 23 work position status inpu...

Page 44: ...iator externally When alarm mute input is active or 60s delay has expired it can remove the alarm 16 Reserved 17 Genset Start Delay Output when start signal is initiated 18 Genset Stop Delay Output wh...

Page 45: ...47 S1 Genset Start When the system type is S1 Gen S2 Gen it controls the S1 genset start 48 S2 Genset Start When the system type is S1 Gen S2 Gen it controls the S2 genset start 49 ATS Power L1 ATS p...

Page 46: ...ontrol When load stepwise switch selects external way load breaker close output 101 External Open Control When load stepwise switch selects external way load breaker open output 102 Reserved 103 Reser...

Page 47: ...d breaker 14 open output 132 Load 15 Close Output Expand output control way load breaker 15 close output 133 Load 15 Open Output Expand output control way load breaker 15 open output 134 Load 16 Close...

Page 48: ...ude themselves Example Contents of OR condition output S1 input port 1 is active Close when OR condition output S1 is active inactive close when active disconnect when inactive Contents of OR conditio...

Page 49: ...lockwise until it reaches proper position Pull the fixing clip backwards towards the back of the module and ensure four clips are inside their allotted slots Turn the fixing clip screws clockwise unti...

Page 50: ...ower Check starting batteries Check controller connection wirings Check DC fuse RS485 comm abnormal Check connection wirings Check setting of COM port is correct or not Check RS485 s A and B connectio...

Reviews: