HMU8-860 ATS Remote Monitoring Controller User Manual Page 38 of 50
No.
Item
Range
Default
Description
3
Comm.
Module
Address
(1~254)
106
RS485
network
communication
address.
4
Expand
Output
Ports
(1~16)
1
It can set 16 output ports function and
active type of DOUT16B-2 module.
PT Break Communication Detection Setting
1
PT Break Comm.
Detection
(0~1)
0
0: Disable 1: Enable
When it is enabled, PT break is judged
according to AC sampling voltage,
current.
2
PT Break Delay
(0~60)s
3
When the communication detection is
enabled, PT break sign is detected, PT
break warning is triggered after set
delay time.
3
Max.
Line
Volt
Multiple
(0~1.00)
0.20
It is the multiple that max. line voltage
set value of PT break judgment
accounts for rated voltage.
4
Max.
Current
Multiple
(0~1.00)
0.02
It is the multiple that max. current set
value of PT break judgment accounts
for rated current.
5
Line Volt Amplitude
Difference Multiple
(0~1.00)
0.20
It is the multiple that line voltage
amplitude difference set value of PT
break judgment accounts for rated
voltage.
6
Break Reset Volt
Multiple
(0~1.00)
0.90
It is the multiple that PT break reset
voltage set value accounts for rated
voltage.
6.3
DIGITAL INPUT/OUTPUT FUNCTION DESCRIPTION
6.3.1 INPUT PORTS FUNCTION DESCRIPTION
Table 18 – Function Description of Input Ports
No.
Item
Description
0
Not Used
Input port is invalid.
1
Forced Open
Forced open (non-fire cutoff) only suits for breaker with open
control. When it is active, breaker will transfer to 0 position
whether in manual or auto mode.
2
Remote Start On Load
Genset start output, when mains is normal, genset will close
the breaker.
3
Remote Start Off Load
Genset start output, when mains is normal, mains will close the
breaker.
4
Lamp Test
All LED lights on the panel are illuminated and the backlight of
the LCD is illuminated while the LCD screen is all black.
5
Gen1 Fault Input
In cycle start, if the input is active, S1 Gens start will be
inhibited.