HMU8-860 ATS Remote Monitoring Controller User Manual Page 7 of 50
3
SPECIFICATION
Table 3 – Monitoring Module Parameters
Items
Contents
Working Voltage
DC10V~DC35V continuous power supply, DC reverse connection
protection
Overall Consumption
<6W
RS485 Interface
Isolated, half-duplex, 2400/4800/9600/19200bps baud rate, the
maximum communication distance is 1000m (at 9600bps baud
rate).
Ethernet
Self-adaption 10/100Mbit
CAN BUS Interface
Isolated, the maximum communication distance is 250m, using
Belden 9841 cable or equivalent.
Vibration
Frequency: 5Hz-8Hz
Amplitude: ±7.5mm
Range: 8Hz-500Hz
Fixed acceleration: 2g
IEC60068-2-6
Shock
Acceleration: 50g
Pulse continuous time: 11ms
Waveform: half-sine
Finish the shock test from three directions. There are total 18
shocks per test.
IEC60068-2-27
Collision
Acceleration: 20g
Pulse continuous time: 16ms
Waveform: half-sine
IEC60255-21-2
Case Dimension
221mm x 163mm x 51mm
Panel Cutout
205mm x 147mm
Working Temperature
(-25~+70)°C
Working Humidity
(20~93)%RH
Storage Temperature
(-30~+80)°C
Protection Level
Front Panel: IP65, when a waterproof rubber ring is installed
between the controller and the panel.
Rear Panel: IP20
Weight
1.3kg