HMU8-860 ATS Remote Monitoring Controller User Manual Page 25 of 50
No.
Item
Range
Default
Description
RS485-4 Setting (Reserved)
1
RS485-4 Module
Address
(1-254)
001
The module address of current RS485
interface is not used when communicating
with the master control module.
2
RS485-4
Baud
Rate
(0-3)
2
0: 2400bps
1: 4800bps
2: 9600bps
3: 19200bps
3
RS485-4 Parity Bit
(0-2)
0
0: None
1: Odd Parity
2: Even Parity
4
RS485-4 Stop Bit
(1-2)
2
1: 1 Bit
2: 2 Bits
ETHERNET Setting (Reserved)
1
Network
Communication
Enable
(0-1)
0
0: Disable
1: Enable
2
IP Address
192.168.010.025
3
Subnet Mask
255.255.255.000
4
Gateway
192.168.010.001
5
DNS Address
211.138.024.066
6.2
PARAMETER CONTENTS AND SCOPES OF MASTER CONTROL MODULE
Table 17 – Parameter Contents and Scopes
No.
Item
Range
Default
Description
AC Setting
1
S1 Volt Normal
(0-3600)s
10
The delay from S1 voltage abnormal to
normal.
2
S1 Volt Abnormal
(0-3600)s
5
The delay from S1 voltage normal to
abnormal.
3
S2 Volt Normal
(0-3600)s
10
The delay from S2 voltage abnormal to
normal.
4
S2 Volt Abnormal
(0-3600)s
5
The delay from S2 voltage normal to
abnormal.
5
Master Set
(0~1)
0
0: S1 Master 1: S2 Master
6
System Type
(0~3)
0
0: S1 Mains S2 Gen;
1: S1 Gen S2 Mains;
2: S1 Mains S2 Mains;
3: S1 Gen S2 Gen.
7
AC System
(0~3)
1
0: 3 Phase 4 Wire (3P4W)
1: 3 Phase 3 Wire (3P3W)
2: 2 Phase 3 Wire (2P3W)