HMU8-860 ATS Remote Monitoring Controller User Manual Page 40 of 50
No.
Item
Description
30
Auto
Transfer/Restore
Input
Auto trans. auto restore when active and auto trans.
non-restore when inactive.
31
S1 Open Input
QS1 open feedback input.
32
S2 Open Input
QS2 open feedback input.
33
Remote Control Inhibit
Remote control operation is inactive when input is active.
34
S1 PT Break
S1 PT secondary coil break input.
35
S2 PT Break
S2 PT secondary coil break input.
36
QTIE Closed Input
QTIE closed status input.
37
QTIE Trip Fault
QTIE trip fault input.
38
QS1 Closed Status at
Contact Side
QS1 closed status of bustie breaker another side in 4-incoming
2-bustie scheme.
39
QS2 Closed Status at
Contact Side
QS2 closed status of bustie breaker another side in 4-incoming
2-bustie scheme.
40
External Closed Status
When the external stepwise switch is selected, switch device
will close.
41
Reserved
42
S1 Closed Input
QS1 Closed feedback input.
43
S2 Closed Input
QS2 Closed feedback input.
44
Reserved
45
Reserved
46
Reserved
47
Reserved
48
Reserved
49
Reserved
50
Reserved
51
Reserved
52
Load 1 Close Status
Load breaker 1 closed status input.
53
Load 1 Work Position
Status
Load breaker 1 work position status input.
54
Load 1 Test Position Status Load breaker 1 test position status input.
55
Load 1 Breaker Trip
Load breaker 1 trip fault input.
56
Load 2 Close Status
Load breaker 2 closed status input.
57
Load 2 Work Position
Status
Load breaker 2 work position status input.
58
Load 2 Test Position Status Load breaker 2 test position status input.
59
Load 2 Breaker Trip
Load breaker 2 trip fault input.
60
Load 3 Close Status
Load breaker 3 closed status input.
61
Load 3 Work Position
Status
Load breaker 3 work position status input.
62
Load 3 Test Position Status Load breaker 3 test position status input.
63
Load 3 Breaker Trip
Load breaker 3 trip fault input.
64
Load 4 Close Status
Load breaker 4 closed status input.
65
Load 4 Work Position
Status
Load breaker 4 work position status input.