HMU8-860 ATS Remote Monitoring Controller User Manual Page 48 of 50
No.
Items
Description
157
Reserved
158
Reserved
159
Reserved
6.3.3 CUSTOM COMBINED OUTPUT
Defined combination output is composed by 3 parts, OR condition output S1, S2, AND condition
output S3.
S1
or
S2 is
TRUE
, while S3 is
TRUE
, defined combination output is outputting;
S1 and S2 are
FALSE
, or S3 is
FALSE
, defined combination output is not outputting.
NOTE1:
S1, S2, S3 can be set as any contents except for “defined combination output” in the output setting.
NOTE2:
3 parts of defined combination output (S1, S2, and S3) couldn’t include or recursively include themselves.
Example,
Contents of OR condition output S1: input port 1 is active;
Close when OR condition output S1 is active /inactive: close when active (disconnect when inactive);
Contents of OR condition output S2: input port 2 is active;
Close when OR condition output S2 is active /inactive: close when active (disconnect when inactive);
Contents of ANDcondition output S3: input port 3 is active;
Close when AND condition output S3 is active /inactive: close when active (disconnect when inactive);
When input port 1 active or input port 2 active, if input port 3 is active, defined combination output is outputting; If input port
3 inactive, defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, defined combination output is not
outputting.