HMU8-860 ATS Remote Monitoring Controller User Manual Page 27 of 50
No.
Item
Range
Default
Description
2
Fixed C/O Time
(0~1)
0
0: Disable 1: Enable
Disable: The output time is depended
on the close status; the longest output
time is the set c/o time.
Enable: The output time lasts for the
preset time.
3
Close Delay
(0.1~20.0)s
5.0
Pulse time of close relay.
4
Open Delay
(0.1~20.0)s
5.0
Pulse time of open relay.
5
Transfer Rest
(0~9999)s
1
Delay time from S1 open to S2 close or
from S2 open to S1 close.
6
Again Close Delay
(0~20.0)s
0.0
When the breaker fails to open for the
first time, then the module will close
for the second time and the Again
Close Delay begins, after the delay has
expired, if it still fails to open for the
second time, the module will send out
fail to open alarm.
7
Again Open Delay
(0~20.0)s
0.0
When the breaker fails to close for the
first time, then the module will open for
the second time and the Again Open
Delay begins, after the delay has
expired, if it still fails to close for the
second time, the module will send out
fail to close alarm.
8
Type Setting
(0~1)
0
0: 2-breaking 1: 1-breaking
9
Forced Open Action (0~1)
0
0: Warning Alarm 1: Fault Alarm
10
Continuous Close
(0~1)
0
0: Disable 1: Enable
When continuous close is active, it
needs to be enabled, and close time
and open time are inactive.
11
QTIE Enable
(0~1)
0
0: Disable 1: Enable
When bustie breaker control is
required, it needs to be enabled.
Genset Setting
1
Start Delay
(0-9999)s
1
When the genset is ready to start, start
delay begins, after the delay has
expired, start signal will be initiated.
2
Stop Delay
(0-9999)s
5
When the genset is ready to stop, stop
delay begins, after the delay has
expired,
start
signal
will
be
disconnected.
3
Two Gensets Start
Mode
(0~3)
0
0: Cycle Run;
1: Master-Slave Run;