HMU8-860 ATS Remote Monitoring Controller User Manual Page 21 of 50
Before entering the parameter configuration interface of the master control module, the
monitoring module will first read the parameters of the master control module. If communication
fails at this time, the monitoring module will load the factory default parameter values of the master
control module.
The parameter configuration steps of the master control module are as follows:
1)
Select parameters to be configured by the tree diagram;
2)
Set parameters to be changed in the right window. Press the numeric keypad key when
necessary to pop up the numeric keypad
3)
After the parameter configuration, click the parameter write key to write the parameter.
Before writing, a password dialog box will pop up. After entering the correct password
of the master control module, the parameters can be written successfully; otherwise, it
cannot be written. After the correct password is inputted and held for 5 minutes, within
which time the configuration can be repeated without re-entering the password.
4)
After the parameters are written, click the exit key to exit the interface.
NOTE1:
The default password of the master control module is "01234". If you forget the password, please contact
the manufacturer.
NOTE2:
In the process of parameter configuration, if communication fails and then returns to normal, the
monitoring module will re-read and load the parameter configuration of the master control module.
NOTE3:
The monitoring module cannot configure custom character string description parameters of master
control module.
Attentions:
a)
Please modify the internal parameters of the controller in standby mode (eg: programmable
input, output configuration, various delays, etc.), otherwise n alarm or other abnormal
phenomena may occur.
b)
Higher limit value must be greater than lower limit value, such as over voltage limit value
must be greater than under voltage limit value, otherwise both over voltage and under
voltage may occur at the same time.
c)
When setting the warning alarm, please set the return value correctly, otherwise it will fail to
alarm normally. When setting over limit warning, the return value should be less than the set
value; When setting under limit warning, the return value should be greater than the set
value.
d)
The programmable input port 1-12 cannot be set to the same item, otherwise the correct
function will not appear, while the programmable output port 1-13 can be set to the same
item.
4.3.3
ADVANCED PARAMETER CONFIGURATION
Press
key to enter advanced parameter configurationinterface, which includes event log
clear of HAT860 master control module, HMU8-860 default factory value, standard value and remove
UI resource. Part of the items need to enter a specific password to access, if necessary, please
contact the manufacturer.