Section 4
4.1
MAINTENANCE PROCEDURES
General
FY303
Profibus to Valve Positioners are extensively tested and inspected before delivery to the end
user. Nevertheless, during their design and development, consideration was given to the possibility
of repairs by the end user, if necessary.
In general, it is recommended that the end user do not try to repair printed circuit boards. Instead,
he should have spare circuit boards, which may be ordered from Smar whenever necessary.
DIAGNOSTICS
SYMPTOM
PROBABLE ERROR SOURCE
POSITION
SHOWN ON DISPLAY
Positioner Connections
Check wiring polarity and continuity.
Power Supply
Check the minimum voltage signal equal 9 Volts.
Electronics Failure
Check circuit boards for bad connections and replace them for spare boards.
NO
COMMUNICATION
Network Connection
Check network connections: equipment, power supply, couplers, links, and terminators.
Network Impedance
Check network impedance (power supply and terminators impedance).
Positioner Configuration
Check the configuration of the positioner communication parameters.
Network Configuration
Check the network communication configuration.
Electronics Failure
Try spare parts in the positioner circuits.
NO RESPONSE
TO INPUT SIGNAL
Pressure Output Connections
Check up on air leaks.
Air Supply Pressure
Check the air supply pressure. The input pressure to
FY303
shall be between 20 psi and
100 psi.
Calibration
Check the positioner calibration points.
Obstructed Restriction and/or Blocked Output
Observe the following procedures described in this Manual: OUTPUT CONNECTIONS
and RESTRICTION CLEANING.
OSCILLATING
ACTUATOR
Calibration
Adjust parameter Kp.
Adjust parameter Tr.
SLOW ACTUATOR
RESPONSE
Adjustment Parameters are Too Low
Adjust parameter Kp.
TOO FAST ACTUATOR
RESPONSE
Adjustment Parameters are Too High
Adjust parameter Kp.
Table 4.1 - FY303 Diagnostics
If the problem is not presented in the table above follow the Note below:
Summary of Contents for fy303
Page 1: ...OPERATION MAINTENANCE AND INSTRUCTION MANUAL Profibus PA Valve Positioner JUL 16 F Y 3 0 3 M E...
Page 7: ...Kpuvcnncvkqp Hnqyejctv XKK Kpuvcnncvkqp Hnqyejctv...
Page 8: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK...
Page 20: ...FY303 Operation Maintenance and Instructions Manual 1 12...
Page 26: ...FY303 Operation Maintenance and Instructions Manual 2 6...
Page 69: ...Configuration 3 43 Figure 10 Sensor Pressure Configuration Data...
Page 70: ...FY303 Operation Maintenance and Instructions Manual 3 44...
Page 88: ...FY303 Operation Maintenance and Instructions Manual 5 6...
Page 94: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C08...
Page 95: ...Egtvkhkecvkqpu Kphqtocvkqp C09 Eqpvtqn Ftcykpi FM Approvals Factory Mutual...
Page 96: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0 CSA Canadian Standards Association...
Page 97: ...Egtvkhkecvkqpu Kphqtocvkqp C0...
Page 98: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C032...
Page 114: ...6 Mounting Instructions...