Configuration
3.23
After user confirmation, the positioner comes to the normal operation.
NOTE
The calibration unit is always percentage (%). It is also recommendable, before a new calibration, to save the
existing trim data by means of parameter BACKUP_RESTORE, using the option "Last Cal Backup".
Temperature Calibration
The parameter CAL_TEMPERATURE can be used to trim the temperature sensor located at the
body of positioner in order to improve the accuracy of temperature measurement done by its sensor.
The range accepts from - 40
°
C to + 85
°
C. The parameter SECONDARY_VALUE indicates the
value of such measurement.
Using the Simatic PDM, go to the Device menu and select the "Calibration" menu and then
"Temperature:
Figure 3.12 - FY303 Temperature Calibration
The user can set the
desired calibration
temperature point.
Here, the final calibrated
temperature can be
checked.
The user can check the
operation result.
To calibrate, press the key
"write".
Summary of Contents for fy303
Page 1: ...OPERATION MAINTENANCE AND INSTRUCTION MANUAL Profibus PA Valve Positioner JUL 16 F Y 3 0 3 M E...
Page 7: ...Kpuvcnncvkqp Hnqyejctv XKK Kpuvcnncvkqp Hnqyejctv...
Page 8: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK...
Page 20: ...FY303 Operation Maintenance and Instructions Manual 1 12...
Page 26: ...FY303 Operation Maintenance and Instructions Manual 2 6...
Page 69: ...Configuration 3 43 Figure 10 Sensor Pressure Configuration Data...
Page 70: ...FY303 Operation Maintenance and Instructions Manual 3 44...
Page 88: ...FY303 Operation Maintenance and Instructions Manual 5 6...
Page 94: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C08...
Page 95: ...Egtvkhkecvkqpu Kphqtocvkqp C09 Eqpvtqn Ftcykpi FM Approvals Factory Mutual...
Page 96: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0 CSA Canadian Standards Association...
Page 97: ...Egtvkhkecvkqpu Kphqtocvkqp C0...
Page 98: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C032...
Page 114: ...6 Mounting Instructions...