FY303 – Operation, Maintenance and Instructions Manual
4.2
NOTE
The Factory Init should be tried as a last option to recover the equipment control when the equipment presents
some problem related to the function blocks or the communication.
This operation must only be carried out
by authorized technical personnel and with the process offline, since the equipment will be configured
with standard and factory data.
This procedure resets all the configurations run on the equipment, after which a partial download should be
performed. With exception to the equipment physical address and the GSD identifier number selector
parameter. After doing this, all configurations must be remade according to their applications.
Two magnetic tools should be used to this effect. On the equipment, withdraw the nut that fixes the
identification tag on the top of the housing, so that access is gained to the "S" and "Z" holes.
The operations to follow are:
1) Switch off the equipment, insert the magnetic tools and keep them in the holes (the magnetic end in the
holes);
2) Feed the equipment;
3) As soon as Factory Init is shown on the display, take off the tools and wait for the "5" symbol on the right
upper corner of the display to unlit, thus indicating the end of the operation.
This procedure makes effective the entire factory configuration and will eliminate eventual problems with the
function blocks or with the equipment communication.
Note that this procedure must be performed by authorized personal only and with the process switched off,
since the equipment will be configured with standard and factory data.
Disassembly Procedure
Make sure to disconnect power supply and supply pressure before disassembling the positioner.
TRANSDUCER
To remove the transducer from the electronic housing, the electrical connections (in the field
terminal side) and the main board connector must be disconnected.
Loosen the hex screw (6) and carefully unscrew the electronic housing from the transducer,
observing that the flat cable is not excessively twisted.
WARNING
Do not rotate the electronic housing more than 270° without disconnecting the electronic circuit from the power
supply.
Figure 4.1 - Transducer Rotation
NOTE
The numbers indicated between parentheses refer to Figure 5.4 – Exploded View
.
Summary of Contents for fy303
Page 1: ...OPERATION MAINTENANCE AND INSTRUCTION MANUAL Profibus PA Valve Positioner JUL 16 F Y 3 0 3 M E...
Page 7: ...Kpuvcnncvkqp Hnqyejctv XKK Kpuvcnncvkqp Hnqyejctv...
Page 8: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK...
Page 20: ...FY303 Operation Maintenance and Instructions Manual 1 12...
Page 26: ...FY303 Operation Maintenance and Instructions Manual 2 6...
Page 69: ...Configuration 3 43 Figure 10 Sensor Pressure Configuration Data...
Page 70: ...FY303 Operation Maintenance and Instructions Manual 3 44...
Page 88: ...FY303 Operation Maintenance and Instructions Manual 5 6...
Page 94: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C08...
Page 95: ...Egtvkhkecvkqpu Kphqtocvkqp C09 Eqpvtqn Ftcykpi FM Approvals Factory Mutual...
Page 96: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0 CSA Canadian Standards Association...
Page 97: ...Egtvkhkecvkqpu Kphqtocvkqp C0...
Page 98: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C032...
Page 114: ...6 Mounting Instructions...