FY303 – Operation, Maintenance and Instructions Manual
3.34
Self-Calibration using Local Adjustment
This process is necessary to find the position values at which the valve is considered fully open or
close. This operation can be done using the
Configuration Tool
or the Local Adjustment. The
FY303
automatically finds the fully open and closed positions of a valve, but the user may also set a
narrower range of operation should he like to. Before making the Auto-Setup, select the type of
valve through the parameter VALVE_TYPE choosing between "Linear or Rotary" options.
The setup operation can be started writing "Enable" (2) on the parameter SETUP, so the positioner
will execute immediately the operation of auto-setup for approximately 2 to 5 minutes depending on
the type of valve, other configured parameters and function blocks used in the positioner.
The process will be finished when the SETUP parameter will indicate "Disable" (0) automatically
during the operation of reading.
NOTE
This operation should be performed off-line or with the process shut down to be sure that the plant operation
is not disturbed, due the valve will be moved between the fully open and close points in order to reach the
better adjustment.
NOTE
In case of oscillation, decrease the gain of valve, acting on the SERVO GAIN parameter.
If the valve could be out-of-control after its operation, please, repeat the Self-Calibration operation again.
Hall's Offset Compensation without Magnet Part
Before installing the magnet to the positioner, write "Enable" on the menu Factory Hall Offset at
Device menu and wait until the configuration tool set it back to "Disable" indicating end of its process
of Hall's Offset compensation.
Figure 3.31 - Enabling the Hall's Offset Compensation
Figure 3.32 - Disabling the Hall's Offset Compensation
Summary of Contents for fy303
Page 1: ...OPERATION MAINTENANCE AND INSTRUCTION MANUAL Profibus PA Valve Positioner JUL 16 F Y 3 0 3 M E...
Page 7: ...Kpuvcnncvkqp Hnqyejctv XKK Kpuvcnncvkqp Hnqyejctv...
Page 8: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK...
Page 20: ...FY303 Operation Maintenance and Instructions Manual 1 12...
Page 26: ...FY303 Operation Maintenance and Instructions Manual 2 6...
Page 69: ...Configuration 3 43 Figure 10 Sensor Pressure Configuration Data...
Page 70: ...FY303 Operation Maintenance and Instructions Manual 3 44...
Page 88: ...FY303 Operation Maintenance and Instructions Manual 5 6...
Page 94: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C08...
Page 95: ...Egtvkhkecvkqpu Kphqtocvkqp C09 Eqpvtqn Ftcykpi FM Approvals Factory Mutual...
Page 96: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0 CSA Canadian Standards Association...
Page 97: ...Egtvkhkecvkqpu Kphqtocvkqp C0...
Page 98: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C032...
Page 114: ...6 Mounting Instructions...