29
8. Press
Exit
to return to the top menu.
9. When finished with the Pressure Threshold, press the
Exit
button to access the Rod Side
Offset.
10. Press the
Exit
button to return to the top menu.
11. Press the
06 Pressure
button.
12. Press the
Calibrate
button.
13. Enter the weight of the calibration load including all shackles and hook weights, in thousandths
of pounds. Example: Enter 1,400 pounds as 1.4.
14. Pick up the calibration load and allow it to settle. Press the
Yes
button to continue. (Pressing the
No
button will exit the routine.)
15. Measure the radius of the suspended load and enter the measurement.
16. Set down the calibration load, hook block and load handling equipment. Allow it to settle and
press the
Yes
button. Pressing the
No
button will exit the routine.
TEST
SET
TEST
SET
TEST
SET
SkyAzúl, Equipment Solutions
www.skyazul.com
301-371-6126