32
7.3.4 User actions on status display
The user can give the lubrication channel different control commands depending on the lubrication phase with the function
button on the lower right-hand corner of the display.
Interrupt pressurisation
An ongoing pressurization can be interrupted. The button has the text
Stop
. In a dual-line system, the next pressurization starts
on the other line.
Extra lubrication
Extra lubrication can be started, when the channel is not currently pressurizing, in alarm mode or turned off. The button has the
text
Extra
.
In a dual-line lubrication system, both lines are pressurized once. The next line in the set pressurisation sequence is pressurised
first. In a single-line and progressive lubrication system the line is pressurized once.
In pressure transmitter operation, the line pressure discharge is measured. New pressurization starts only after pressure in the
lines falls below the set low limit value.
In pressure switch operation, the system will wait until the pressure in the lines has discharged. A new pressurisation will not
start until after a configured delay.
Reset alarm
In the alarm mode the button has the text
Reset
. When the alarm is reset, pressurization starts on the line that triggered the
alarm.