7.3.3 Lubrication program phases
Phase code
Phase description
Interval
The time elapsed since the start of the previous pressurization is
presented in minutes.
Interlocking
Interlocking input is in status ON. The interval calculation has been
interrupted.
Closed
The lubrication channel is not in operation. Pressurization time has been
set to 0s.
Discharging
The program waits for line pressure discharge below the set low limit
before starting pressurization.
Waiting
Channel pressurization is starting, but the channel will first wait for the
pressurization to end in another lubrication channel.
Delay
The display shows, in a lubrication system equipped with pressure
switches, the remaining waiting time between two pressurization steps in
the extra lubrication.
Pressuring L1
Pressurization is in progress in line 1. The elapsed pressurisation time is
shown in seconds.
Pressuring L2
As above, line 2.
Air alarm
The air pressure switch has triggered an alarm in the grease spraying
system.
Pressure alarm (ALP) L1
The pressure has not risen to the set high limit value during previous
pressurization on line 1.
Pressure alarm (ALP) L2
As above, line 2.
Pressure alarm (AHP) L1
The pressure has been above the set low limit in line 1 or 2 when
pressurization started in line 1.
Pressure alarm (AHP) L2
As above, line 2.
Low level alarm
Alarm from the lubricant reservoir9s low level switch.
Pulse alarm
Pulse (progressive distributor piston detector) amount alarm in a
progressive system. The set pulse amount was not reached during
pressurization time.