6
6. CONFIGURATION
The installer when starting the system does the
configuration.
Press the “+” and “-” keys at the same time to
access it. The “C” key is used to go from one code to
another and the “+” and “-” are used to modify values
as well as the YES and NO answers. Press the “C”
and “+” keys at the same time to escape
configuration and go back to the main menu.
The first configuration code to be completed is
coding number 16, which is used to configure how the
outlets have to work. There are 7 possible
configurations, as shown at Table 1. It is essential to
put a valid code in this section. If there is no valid
value, the programmer does not accept the petitions
of engine starting and the screen blinks constantly.
Table 1 Outlet configuration.
Configuration
number
Outlet
number
Outlet function
1
4
5
6
Fertiliser
Pump
Breakdown indication
2
4
5
6
Fertiliser
Warm-up
Breakdown indication
3
4
5
6
Fertiliser
Pump
Warm-up
4
4
5
6
Warm-up
Pump & unique sector
Breakdown indication
5
4
5
6
Sector 1
Sector 2
Pump
6
4
5
6
Sector 1
Sector 2
Breakdown indication
7
4
5
6
Sector 1
Sector 2
Warm-up
Figure 7. Configuration diagrams
The following graphics show the working of the
outlets according to the chosen option.
CONFIGURATION 1
CONFIGURATION 2
CONFIGURATION 3
CONFIGURATION 4