10
The remaining codes are to be configured next.
Table 3 Configuration sections
CODE FUNCTION
01
Post-irrigation time: is the time in advance
the fertilisation must stop before the
irrigation. From 0 to 250 minutes.
02
Erase engine working time?: answer YES or
NO using the “+” or “-“ keys respectively.
03
Starting time: is the time the activation of the
engine takes. From 0 to 250 seconds.
04
Number of starting attempts: is the starting
attempts it will do while it is not detected
that the engine has started. From 1 to 9.
05
Time between starts: is the pause left
between the starting attempts. From 0 to
250 seconds.
06
Warm-up time: (only for those who need it).
From 0 to 250 seconds.
07
Stop time: duration of the electrovalve
activation (N.A.), or the electromagnet, to
stop the engine. From 0 to 250 seconds.
08
Time between engine and pump starts:
(only for generators) is the time it will wait
before the electropump is activated, from
the time the engine was started.
09
Time between pump and engine stops:
(only for generators) is the time that will go
by from the electropump stop to the engine
stop. From 0 to 250 seconds.
10
Delay in the breakdown detection: indicate
how long input 4 must be activated for the
programmer to recognise that a breakdown
has taken place and the engine is stopped.
From 0 to 250 seconds.
11
Delay in the detection of engine breakdown:
indicate the delay in the detection of input 3,
in order to detect a breakdown in the oil
pressure (diesel) or in the battery charge
(petrol). From 0 to 250 seconds.
12
Delay in the activation of input 1 (Start or
Start/Stop, according to code 14). From 0 to
250 seconds.
13
Delay in the activation of input 2 (Stop or
Conditional Stop, according to code 14).
From 0 to 250 seconds.
14
Functions inputs 1 and 2: Answer YES if
input number 1 is to work as start/stop and
input number 2 as conditional stop (or it is
not going to be used). Answer NO if input
number 1 is to work only as start and the
stop is to be done by input number 2.
15
Engine only working if input 1 and
programme are activated?: answer YES or
NO, according to table number 2.
16
Outlet configuration: according to table 1.
From 1 to 7.
NOTES:
At code 15, if the programme arrives before the input, this
one is activated and it proceeds as if the engine was working
(programme time goes on). In this way, if input number 1 is
activated after the programme has been activated, the remaining
irrigation will take place. In the same way, if the engine stops
because there is no signal at input 1, and it appears again, the
engine will start again. But this code is not respected if the
programme or sector activation has been done manually. In this
case, whatever the answer to this question is, the engine starts
and if there is another stop, the programme is deactivated.