25
When the test has been completed satisfactorily, repeat with any extractor fans in the premises running on the
highest setting, and any communicating doors open.
Finally, repeat with all doors open.
DO NOT
allows the fire to be used until the test is satisfactorily passed.
All instructions must be handed to the user for safekeeping.
Show the customer how to light and operate the fire.
After commissioning the appliance, the customer should be instructed on the safe use of the appliance
and the informed for the need of regular servicing.
Frequency of service depends on usage, but
MUST
be carried out at least once annually.
Cleaning of the fire may be achieved when the fire is cold using a damp cloth and mild detergent on most
surfaces, with the exception of the ceramic fuel bed.
A soft brush i.e. paint brush may be used to clean the ceramic fuel bed taken care not to use excessive
pressure.
Scratched and other superficial damage to the matt black paintwork of the appliance can be covered
with matching heatproof spray.
Use only the manufacturers’ recommended spray paint.
Paint only when the fire is OFF and cold. Always mask off the surrounding area to prevent contamination
with overspray.
Ventilate the room during the use of the spray. DO NOT attempt to spray paint the coals or ceramics, or
wash them in water.
Advise that the fire will emit a “newness” smell for a time after initial commissioning and that extra
ventilation may be needed during this time.
Advise that the fire is fitted with a spillage safety device (O.D.S.). If the fire shuts down, this system may
be in operation.
If spillage is suspected, SWITCH APPLIANCE OFF and call in the installer to investigate any problems
.
FIG 1
Hold smoke match in position 10mm inside
and down from top face of the central slot
SECTION 14: BRIEFING THE CUSTOMER