P1 malfunction: High pressure protection
LED displays P1
High pressure protection
Judge whether the wiring connection is correct.
Judge wire body is broken or not.
YES
NO
Connect again.
To confirm: short-circuit high pressure switch and check whether
the system can operate normally or not.
NO
Replace high pressure switch.
YES
Check whether the cooling system is normal or not.
Replace main PCB.
NO
Check whether pressure of the system is too high.
YES
Stop the system.
NO
Whether side air duct of outdoor unit meets the standard.
NO
Rectify the air duct
YES
Whether the heat exchanger needs cleaning.
YES
Clean.
NO
Whether the pipeline is blocked.
YES
Rectify the pipeline.
Judge the circulation water pump is damaged or not.
Repair or replace the water pump
YES
Whether plate heat exchanger is fouling or blocked severely
Clean or replace heat exchanger .
YES
NO
NO
77
Summary of Contents for SCV-100EA
Page 1: ...SCV xxEA SERVICE MANUAL AIR COOLED MINI CHILLER UNIT AIR CONDITIONING...
Page 16: ...7 Wiring Diagram SCV 50EA SCV 70EA 14...
Page 17: ...SCV 100EA 15...
Page 18: ...SCV 120EA SCV 140EA SCV 160EA 16...
Page 28: ...11 Water Pressure Drop SCV 50EA SCV 70EA SCV 100EA Heat exchanger pressure drop water side 26...
Page 29: ...SCV 120EA SCV 140EA 27...
Page 30: ...SCV 160EA 28...
Page 88: ...18 Optional Accessories No Name Specification Remark 1 Wired controller KJR 120F Customized 86...
Page 91: ...Exploded view of unit SCV 50EA 22 7 22 6 22 5 22 4 22 2 22 1 22 3 89...
Page 94: ...Exploded view of unit SCV 70EA 22 7 22 6 22 5 22 4 22 2 22 1 22 3 92...
Page 97: ...Exploded view of unit SCV 100EA 25 1 25 2 25 3 25 6 25 7 25 4 25 5 25 9 25 8 95...
Page 100: ...Exploded view of unit SCV 120EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 98...
Page 103: ...Exploded view of unit SCV 140EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 101...
Page 106: ...Exploded view of unit SCV 160EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 104...