17.4 Error code table
5/7kW
Error
Code
Content
Note
E9 EEPROM
malfunction
The same as
10-16kW
H0
Communication malfunction between main chip and IPDU.
E4
T3,T4 sensor malfunction
E5
Voltage protection malfunction
E6
DC fan motor malfunction
EA
A fan in the A region run for more than 5 minutes in heating mode
Eb
There are two times E6 fault in 10 minutes (recovery after power off)
HH
Inlet water temperature sensor malfunction for 5/7kW models.
5/7kW
EC
Outlet water temperature sensor malfunction (5/7kW)
C0
Temperature sensor malfunction of plate heat exchanger for 5/7kW.
P1 High
pressure
protection
The same as
10-16kW
P2 Low
pressure
protection
P3
Current protection of the compressor
P4
Discharged temperature protection
P5
T3 high temperature protection of outdoor condenser
P6
IPDU module protection
P8 Typhoon
protection
CH
Protection when temperature difference between inlet & outlet water in heating mode is too
large for 5/7kW
5/7kW
CL
Protection when temperature difference between inlet & outlet water in cooling mode is too
large for 5/7kW.
CP
Anti-freeze protection of plate heat exchanger for 5/7kW
Pb
System anti-freeze protection
The same
as 10-16kW
C8
Water flow switch protection malfunction
PH
Protection when water temperature in heating mode is too high for 5/7kW.
5/7kW
dF Defrosting
The same as
10-16kW
d8 Remote
control
72
Summary of Contents for SCV-100EA
Page 1: ...SCV xxEA SERVICE MANUAL AIR COOLED MINI CHILLER UNIT AIR CONDITIONING...
Page 16: ...7 Wiring Diagram SCV 50EA SCV 70EA 14...
Page 17: ...SCV 100EA 15...
Page 18: ...SCV 120EA SCV 140EA SCV 160EA 16...
Page 28: ...11 Water Pressure Drop SCV 50EA SCV 70EA SCV 100EA Heat exchanger pressure drop water side 26...
Page 29: ...SCV 120EA SCV 140EA 27...
Page 30: ...SCV 160EA 28...
Page 88: ...18 Optional Accessories No Name Specification Remark 1 Wired controller KJR 120F Customized 86...
Page 91: ...Exploded view of unit SCV 50EA 22 7 22 6 22 5 22 4 22 2 22 1 22 3 89...
Page 94: ...Exploded view of unit SCV 70EA 22 7 22 6 22 5 22 4 22 2 22 1 22 3 92...
Page 97: ...Exploded view of unit SCV 100EA 25 1 25 2 25 3 25 6 25 7 25 4 25 5 25 9 25 8 95...
Page 100: ...Exploded view of unit SCV 120EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 98...
Page 103: ...Exploded view of unit SCV 140EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 101...
Page 106: ...Exploded view of unit SCV 160EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 104...