4. Specifications
Model
Power supply
V-Ph-Hz
220-240, 1, 50
220-240, 1, 50
Cooling*(1)
Capacity kW
5.0
7.0
Input kW
1.55
2.25
Cooling*(2)
Capacity kW
6.57
7.88
Input kW
1.27
1.84
Heating*(3)
Capacity kW
5.5
8.0
Input kW
1.7
2.5
Heating*(4)
Capacity kW
6.32
8.29
Input kW
1.52
2.13
EER*(1) kW/kW
3.23
3.11
EER*(2) kW/kW
5.16
4.28
Max. input consumption
kW
2.8
3.0
Max. input current
A
14.6
15.6
Compressor
Model
SNB172FJGMC
SNB172FJGMC
Type
ROTARY
ROTARY
Brand
Mitsubishi Electric
Mitsubishi Electric
Capacity kW
5.46
5.46
Input kW
1.64
1.64
Rated load current
A
8.1
8.1
Locked rotor Amp
A
29.5
29.5
Thermal protector
Inner Inner
Refrigerant oil
ml
FV50S,400
FV50S,400
Outdoor fan
motor
Model
WZDK170-38G-1 WZDK170-38G-1
Type
DC Motor
DC Motor
Brand
NIDEC SHIBAURA
NIDEC SHIBAURA
Input
W 170
170
Speed
r/min 820
820
Outdoor coil
Number of rows
2
2
Tube pitch(a)× row pitch(b)
mm
22×19.05
22×19.05
Fin spacing
mm
1.6
1.6
Fin type
Hydrophilic aluminum foil
Hydrophilic aluminum foil
Tube outside dia. and type
mm
φ
7.94
φ
7.94
Inner grooved copper tube
Inner grooved copper tube
Coil length ×height
mm
885×880
885×880
Number of circuits
6
6
Water pump
Type
RS15/6-3-WILO
RS15/6-3-WILO
Input (H/M/L)
W
93/67/46
93/67/46
Pumping head
m
5.5
5.5
Outdoor air flow
m
3
/h 5100
5100
Throttle
EXV+capillary
EXV+capillary
Outdoor noise level (sound pressure)*(3)
dB(A)
58
58
Water flow
m
3
/h 0.86
1.20
The plate heat-exchanger water pressure
drop
kPa 15
15
The Max. and Min. water inlet pressure
kPa
500/150
500/150
Outdoor
unit
Net dimension (W×H×D)
mm
990×966×354
990×966×354
Packing dimension
(W×H×D)
mm 1120×1100×435
1120×1100×435
Net/ Gross weight
kg
81/91
81/91
Refrigerant
Type
R410A
R410A
Charged volume
kg
2.5
2.5
Connection
wiring
Power wire mm
2
3×2.5
3×2.5
Signal wire
mm
2
3×0.75
3×0.75
Pipe
diameter
Water inlet/outlet
inch
1’’
1’’
Control
Wired controller
Wired controller
Ambient temperature
℃
Cooling:
-5
℃
~46
℃
; Heating: -15-27
℃
(Antifreeze must be added below 5
℃
)
Water outlet temperature range
℃
Cooling:
4~20
℃
; Heating: 30~55
℃
Note: Specifications are based on the following conditions:
1. Cooling: (*1) chilled water inlet/outlet temperature: 12/7°C,outdoor ambient temperature 35°C DB.
(*2) chilled water inlet/outlet temperature: 23/18°C,outdoor ambient temperature 35°C DB.
SCV-50EA SCV-70EA
8
Summary of Contents for SCV-100EA
Page 1: ...SCV xxEA SERVICE MANUAL AIR COOLED MINI CHILLER UNIT AIR CONDITIONING...
Page 16: ...7 Wiring Diagram SCV 50EA SCV 70EA 14...
Page 17: ...SCV 100EA 15...
Page 18: ...SCV 120EA SCV 140EA SCV 160EA 16...
Page 28: ...11 Water Pressure Drop SCV 50EA SCV 70EA SCV 100EA Heat exchanger pressure drop water side 26...
Page 29: ...SCV 120EA SCV 140EA 27...
Page 30: ...SCV 160EA 28...
Page 88: ...18 Optional Accessories No Name Specification Remark 1 Wired controller KJR 120F Customized 86...
Page 91: ...Exploded view of unit SCV 50EA 22 7 22 6 22 5 22 4 22 2 22 1 22 3 89...
Page 94: ...Exploded view of unit SCV 70EA 22 7 22 6 22 5 22 4 22 2 22 1 22 3 92...
Page 97: ...Exploded view of unit SCV 100EA 25 1 25 2 25 3 25 6 25 7 25 4 25 5 25 9 25 8 95...
Page 100: ...Exploded view of unit SCV 120EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 98...
Page 103: ...Exploded view of unit SCV 140EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 101...
Page 106: ...Exploded view of unit SCV 160EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 104...