8. Electric Characteristics
Model
Outdoor Unit
Power Supply
Compressor
OFM
Hz Voltage
Phase
Min.
Max.
MCA TOCA MFA MSC
RLA kW FLA
SCV-50EA 50Hz
220~240V 1Ph 198V
264V
10.1
14.6
20
29.5
8.1 0.195 1.65
SCV-70EA 50Hz
220~240V 1Ph 198V
264V
10.1
15.6
20
29.5
8.1 0.195 1.65
SCV-100EA 50Hz 220~240V 1Ph 198V
264V
15.1
25.0
30
52 12.1 0.20
1.8
SCV-120EA 50Hz 380~415V 3Ph 342V
456V
8.6
8.9 15
44 6.9 0.20 1.8
SCV-140EA 50Hz 380~415V 3Ph 342V
456V
8.6
9.6 15
44 6.9 0.20 1.8
SCV-160EA 50Hz 380~415V 3Ph 342V
456V
8.6
10.1
15
44 6.9 0.20 1.8
Remark:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Current Amps. (A)
OFM: Outdoor Fan Motor
FLA: Full Load Amps. (A)
kW: Rated Motor Output (kW)
17
Summary of Contents for SCV-100EA
Page 1: ...SCV xxEA SERVICE MANUAL AIR COOLED MINI CHILLER UNIT AIR CONDITIONING...
Page 16: ...7 Wiring Diagram SCV 50EA SCV 70EA 14...
Page 17: ...SCV 100EA 15...
Page 18: ...SCV 120EA SCV 140EA SCV 160EA 16...
Page 28: ...11 Water Pressure Drop SCV 50EA SCV 70EA SCV 100EA Heat exchanger pressure drop water side 26...
Page 29: ...SCV 120EA SCV 140EA 27...
Page 30: ...SCV 160EA 28...
Page 88: ...18 Optional Accessories No Name Specification Remark 1 Wired controller KJR 120F Customized 86...
Page 91: ...Exploded view of unit SCV 50EA 22 7 22 6 22 5 22 4 22 2 22 1 22 3 89...
Page 94: ...Exploded view of unit SCV 70EA 22 7 22 6 22 5 22 4 22 2 22 1 22 3 92...
Page 97: ...Exploded view of unit SCV 100EA 25 1 25 2 25 3 25 6 25 7 25 4 25 5 25 9 25 8 95...
Page 100: ...Exploded view of unit SCV 120EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 98...
Page 103: ...Exploded view of unit SCV 140EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 101...
Page 106: ...Exploded view of unit SCV 160EA 25 1 25 2 25 3 25 4 25 5 25 6 25 7 25 9 25 8 25 10 25 11 104...