SITRANS RD300
A5E31917845
SITRANS RD300 – OPERATING INSTRUCTIONS
Page 79
Select Menu (
SElEct
)
The
Select
menu is used to select the signal input conditioner applied to
the input (linear, square root, programmable exponent, or round
horizontal tank), low-flow cutoff, and analog output programming. The
multi-point linearization is part of the linear function selection.
Note:
Count
menu is only available when
TOTAL
is
enabled. To enable
TOTAL
see Configuring as a Rate/Total
Meter on page 25.
Signal Input Conditioning (
Functn
)
The
Function
menu is used to select the signal input conditioner
applied to the input: linear, square root, programmable exponent, or
round horizontal tank volume calculation. The multi-point linearization is
part of the linear function selection.
Meters are set up at the factory for linear function with 2-point
linearization. The linear function provides a display that is linear with
respect to the input signal.