SITRANS RD300
A5E31917845
SITRANS RD300 – OPERATING INSTRUCTIONS
Page 55
If the backup pump is not able to keep up, and the level
reaches 7000 gallons, relay #4 transfers and starts the main
pump as well.
Relay #2 trips the High Level Alarm at 7500 gallons and resets
at 6900 gallons.
Relay #1 trips the Low Level Alarm at 495 gallons and resets
at 750 gallons.