7ML19985XR82
SITRANS LR560 (FF)
Page EN-7
m
mmmm
Englis
h
Sun Shield
The LR560 display can be protected by an
optional sun shield if the instrument will be
mounted in direct sunlight
Aimer Adjustment
3" flange
4 and 6" flange
1)
For 4" and 6" Aimer: loosen the set screws in the locking ring.
Holding the electronics enclosure firmly, loosen the Aimer locking ring using the supplied
C spanner, until the LR560 drops down slightly. The enclosure can then be turned freely.
2)
Direct SITRANS LR560 so the antenna is pointed at an angle perpendicular to the
material surface, if possible.
3)
When the desired position is reached, re-tighten the locking ring using the C spanner, and
tighten set screws.
4)
For the 3" Aimer flange, tapered split washers with pressure rated versions are provided
to keep nuts and bolts perpendicular to the flange surface.
Aimer
Aiming is not
required for signal
optimization with
78 GHz frequency.
Aiming will assist
in measuring
material in the
cone.