Page EN-12
SITRANS LR560 (FF)
7ML19985XR82
mmmmm
English
To modify a text string
1)
Navigate to the parameter you wish to modify and press to edit it. The string will be
highlighted.
2)
Follow the same steps as above, to add, delete, or modify characters.
Quick Start Wizard
1. Quick Start
1.1. Quick Start Wizard
1)
Press twice to navigate to Quick Start (1.) and open
Quick Start Wizard (1.1.)
2)
At each step, press to accept default values and move
directly to the next item,
or to open Edit mode: the current selection is
highlighted.
3)
Scroll to desired item and press to store the change, then press to continue.
4)
At any time, you can press to go back, or to cancel and return to
Measurement mode.
Vessel
Response Rate
Use a setting just faster than the maximum vessel filling or vessel emptying rate (whichever is
greater).
Note: Default values are indicated by an asterisk (*) in the tables below, unless explicitly
described.
Response Rate
Vessel Fill Rate or Empty Rate per minute
SLOW
0.1 m/min (0.32 ft/min)
MED
*
1.0 m/min (3.28 ft/min)
FAST
10.0 m/min (32.8 ft/min)
Parameter View
Edit mode
Select vessel construction material.
Options
* STEEL
CONCRETE
Sets the reaction speed of the device to
measurement changes in the target range.