Page EN-16
SITRANS LR560 (FF)
7ML19985XR82
mmmmm
English
Configuring a new device
1)
Changing Block Modes
To change any block mode follow the same procedure as for changing Resource Block mode.
To change Resource Block mode
1)
Navigate to Configure/Setup > Resource Block > Operation > Block Mode and click Block
Mode to open the dialog window.
2)
Select the desired Target mode and deselect the other option. Click Apply (the Apply
button is activated when a change is made).
3)
Return to the main menu.
Notes:
• The LR560 FF is shipped with RESOURCE and LTB blocks in Out of Service mode.
• After completing the Quick Start Wizard, via AMS or via local operation, you must
manually put the RESOURCE and LTB blocks into AUTO mode. (An exception is the first
time the Quick Start Wizard is completed via local operation
1)
.)
• Please consult the operating instructions or online help for details on using AMS Device
Manager.
1)
Then the RESOURCE and LTB blocks are automatically returned to AUTO mode.
Note: Resource Block overrides Level Transducer Block. Changing Resource Block mode will
also change Level Transducer Block mode.
Target Mode deselected
Target Mode selected
Apply