7ML19985XR82
SITRANS LR560 (FF)
Page EN-13
m
mmmm
Englis
h
Units
Operation
Low Calibration Point
High Calibration Point
Wizard Complete
To transfer Quick Start values to the device and return to Program menu, press (Finish).
Then press to return to Measurement mode.
Operation
Description
LEVEL (1)
*
Distance from Low Calibration Point to material surface
SPACE (2)
Distance from High Calibration Point to material surface
DISTANCE(3)
Distance from Sensor Reference Point to material surface
Options
BACK, CANCEL, FINISH (Display returns to 1.1 Quick Start Wizard menu when Quick
Start is successfully completed.)
Sensor measurement units.
Values
m, cm, mm, ft, in
Default: m
sensor reference point
(flange face)
High Cal.
Pt.
Distance
Space
Low Cal. Pt.
Level
Distance from Sensor Reference Point to Low
Calibration Point: usually process empty level.
Values
Range: 0.000 to 40.000 m or
0.000 to 100.000 m
Default: 40.000 or 100.000 m
Distance from Sensor Reference Point to High
Calibration Point: usually process full level.
Values
Range: 0.000 to 40.000 m or
0.000 to 100.000 m
Default: 0.000 m