Functions
6-33
7SJ63 Manual
C53000-G1140-C120-1
1
) only available with 79 function is enabled
1202 50-2 PICKUP
0.50 ~ 175.00 A
10.00 A
Pickup setting of the 50-2
element
X X X X X
1203 50-2 DELAY
0.00 ~ 60.00 sec
0.00 sec
Delay setting of the 50-2
element
X X X X X
1204 50-1 PICKUP
0.50 ~ 175.00 A
5.00 A
Pickup setting of the 50-1
element
X X X X X
1205 50-1 DELAY
0.00 ~ 60.00 sec
0.50 sec
Delay setting of the 50-1
element
X X X X X
1207 51 PICKUP
0.50 ~ 20.00 A
5.00 A
Pickup setting of the 51
element
X X X X
1208 51 TIME DIAL
0.05 ~ 3.20 sec
0.50 sec
Time multiplier T Ip, IEC and
User Defined Curves
X
X X
1209 51 TIME DIAL
0.50 ~ 15.00
5.00 sec
Time dial setting, ANSI
X
1210 51 Drop-out
Instantaneous
Disk Emulation
Disk Emulation
Characteristics of 51 dropout
X
X
1211 51 IEC CURVE Normal Inverse
Very Inverse
Extremely Inverse
Long Inverse
Normal Inverse
Characteristic curve (IEC)
X
X
X
X
1212 51 ANSI
CURVE
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inverse
Extremely Inverse
Definite Inverse
Very Inverse
Characteristic curve (ANSI)
X
X
X
X
X
X
X
1213 MANUAL
CLOSE
50-2 Instantaneously
50-1 Instantaneously
51 Instantaneously
Inactive
50-2
Instantaneously
Selection of high speed
tripping element when
manual closing feature is
used
X X X X X
1214 50-2 active
1
)
Always
with 79 active
Always
Criteria for operation of 50-2
element
X X X X X
1230 51/51N
51 user defined
characteristic curve values
X X
1231 MofPU Res T/
Tp
51 reset user defined curve
values
X
Addr.
Setting Title
Setting Options
Default Setting
Comments
Configuration
D
e
finit
e Ti
m
e
Only
IEC
Curv
e
A
N
SI
Curve
U
s
er Def
ined Pick
up
U
s
er def
.
Res
et