Communication via CC-Link
03.99
6SE7087-6NX84-0GB0
Siemens AG
4-4
Operating Instructions
SIMOVERT MASTERDRIVES
4.2
CBL, converter between CC-Link and MASTERDRIVES
CBL converts the CC-Link profile for inverter to the data structure of
SIMOVERT MASTERDRIVES.
It converts the control bits (remote IO bits RYn....) to the bits of the
control word from the converter. In other direction the bits of the status
word are translated to the remote IO bits RXn... . Chapter "Appendix"
describes the rules of bit generation.
The CBL also transports the reference values (setpoint) and the actual
values (incl. monitoring) between CC-Link interface and the dual port
RAM interface of the MASTERDRIVES. CBL translates between the
different data formats by calculating with scaling factors.
The handling of parameters at CC-Link by Command
code execution
is transformed to the PKW task handling with PKW request and reply of
MASTERDRIVES.
remote IO bits
remote register
reference value
(setpoint)
actual values
(incl. monitoring
command code
execution
conversion of
control and status bits
PZD
Channel
PKW
Channel
DPRAM
CC-Link
profile for inverter
CBL
PLC +
CC-Link
MASTER-
DRIVES
Fig. 4-1
CBL converting between CC-Link and MASTERDRIVES
All manuals and user guides at all-guides.com
Summary of Contents for Simovert Masterdrive FANC-SB
Page 8: ...All manuals and user guides at all guides com ...
Page 14: ...All manuals and user guides at all guides com ...
Page 48: ...All manuals and user guides at all guides com ...
Page 58: ...All manuals and user guides at all guides com ...
Page 70: ...All manuals and user guides at all guides com ...
Page 72: ...All manuals and user guides at all guides com ...