03.99
Technical data
Siemens AG
6SE7087-6NX84-0GB0
SIMOVERT MASTERDRIVES
Operating Instructions
7-1
7 Technical
data
Order No.
6SE7090-0XX84-0GB0
Size (length x width)
90 mm x 83 mm
Degree of pollution
Pollution degree 2 to IEC 664-1 (DIN VDE 0110/T1),
Moisture condensation during operation is not permissible.
Mechanical specifications
During stationary use
•
deflection
•
acceleration
During transport
•
deflection
•
acceleration
to DIN IEC 68-2-6 (if board correctly mounted)
0.15 mm in the frequency range 10 Hz to 58 Hz
19.6 m/s
2
in the frequency range > 58 Hz to 500 Hz
3.5 mm in the frequency range 5 Hz to 9 Hz
9.8 m/s
2
in the frequency range > 9 Hz to 500 Hz
Climatic class
Class 3K3 to DIN IEC 721-3-3 (during operation)
Type of cooling
Natural-air cooling
Permissible ambient or cooling-
medium temperature
•
during
operation
•
during
storage
•
during transport
0° C to +70° C (32° F to 158° F)
–25° C to +70° C (-13° F to 158° F)
–25° C to +70° C (-13° F to 158° F)
Humidity rating
Relative humidity
≤
95 % during transport and storage
≤
85 % during operation
(moisture condensation not permissible)
Supply voltage
5 V
±
5 %, max. 500 mA, internally from the basic unit
All manuals and user guides at all-guides.com
all-guides.com
Summary of Contents for Simovert Masterdrive FANC-SB
Page 8: ...All manuals and user guides at all guides com ...
Page 14: ...All manuals and user guides at all guides com ...
Page 48: ...All manuals and user guides at all guides com ...
Page 58: ...All manuals and user guides at all guides com ...
Page 70: ...All manuals and user guides at all guides com ...
Page 72: ...All manuals and user guides at all guides com ...