Start-up of the CBL
03.99
6SE7087-6NX84-0GB0
Siemens AG
5-2
Operating Instructions
SIMOVERT MASTERDRIVES
P053 (parameterizing enable)
This parameter is significant for the CBL if you wish to set or change
parameters of the converter (incl. technology) by means of parameterizing
tasks (PKW task).
In this case, set parameter P053 (see also the parameter list in the instruction
manual of the converter) to an odd value (e.g. 1, 3, 7 etc.). With parameter
P053, you specify the positions (PMU, CBL etc.) from which it is permissible
to change parameters.
E.g.: P053
= 1:
Parameterizing enable only CBL
= 3:
Parameterizing enable CBL+PMU
= 7:
Parameterizing enable CBL+PMU+SST1 (OP)
If the parameter change (= parameterizing enable) is enabled via the CBL
(P053 = 1, 3 etc.), all further parameters can be set from the CC-Link master
via the bus.
P060
Function selection: "Hardware setting" = 4
P711 (CB parameter 1)
Communication speed CC-Link
With this parameter, the data transmission speed on CC-Link can be set. It
has to be the same as the CC-link master.
Default value is 0.
P711
Communication speed
Maximum bus
length
0
156 kbits/s
1200m
1
625 kbits/s
600m
2
2.5 Mbits/s
200m
3
5 Mbits/s
150m
4
10 Mbits/s
100m
Example
P711=2: The communication speed is 2.5 Mbits/s.
All manuals and user guides at all-guides.com
Summary of Contents for Simovert Masterdrive FANC-SB
Page 8: ...All manuals and user guides at all guides com ...
Page 14: ...All manuals and user guides at all guides com ...
Page 48: ...All manuals and user guides at all guides com ...
Page 58: ...All manuals and user guides at all guides com ...
Page 70: ...All manuals and user guides at all guides com ...
Page 72: ...All manuals and user guides at all guides com ...