Communication via CC-Link
03.99
6SE7087-6NX84-0GB0
Siemens AG
4-2
Operating Instructions
SIMOVERT MASTERDRIVES
Device No
Bit name
Description
RYn0
Forward command
(STF)
OFF: Stop command (with STR = OFF)
ON: Forward command
Note: edge sensitive signal (0-1-transition for starting drive)
RYn1
Reverse command
(STR)
OFF: Stop command (with STF = OFF)
ON: Reverse command
Note: edge sensitive signal (0-1-transition for starting drive)
RYn2
High speed (RH)
Fixed setpoint high (refer to parameter P404)
RYn3
Medium speed (RM)
Fixed setpoint medium (refer to parameter P403)
RYn4
Low speed (RL)
Fixed setpoint low (refer to parameter P402)
RYn5
JOG1 mode (JOG1)
Activates JOG mode; speed and direction controlled by signed
integer parameter "JOG Setpoint 1" (in percent); refer to function
diagram at converter documentation.
RYn6
Second
Acceleration/decel.
time Selection (RT)
Selects the data sets with index 1 (RT = 0) or index 2 (RT = 1); here
the user can switch between to data sets (FDS 1 and 2). This sets
contain more than acceleration and decel. time; refer to converter
documentation about "function data set"
RYn7
JOG2 mode (JOG2)
Activates JOG mode; speed and direction controlled by signed
integer parameter "JOG Setpoint 2" (in percent); refer to function
diagram at converter documentation.
RYn8
Option flag 27 (F27)
Additional control bit; refer to chapter 4.11 "Optional flags in CBL
profile"
RYn9
Output stop (MRS)
ON: Output halt
MRS is inverted and routed to OFF2 in control word 1
RYnA
Option flag 28 (F28)
Additional control bit; refer to chapter 4.11 "Optional flags in CBL
profile"
RYnB
Option flag 29 (F29)
Additional control bit; refer to chapter 4.11 "Optional flags in CBL
profile"
RynC
Monitor command
When the monitor command is turned ON, the monitor value is set in
the remote register (RWrm) and the monitoring (RXnC) becomes
ON. The monitor value is constantly changed during ON.
Refer to chapter 4.5 "Monitoring"
RynD
Frequency set
command (RAM)
When the frequency set command is turned ON, the frequency
(RWwm+1) is written to the inverter. When the write is completed, the
frequency setting complete (RXnD) turns ON.
Refer to chapter 4.4 "Setpoint handling"
RynF
Command code
execution request
When the command code execution request is turned ON, the
process corresponding to the command code (RWwm2) is executed.
The command code execution complete (RXnF) turns on after the
command code execution is completed. If a command code
execution error occurs, a value
≥
8000h is set as the reply code
(RWrm2).
Refer to chapter 4.6 "Command code execution"
RY (n+1)8
Initial data processing
complete flag
When the initial data processing is requested (RX(n+1)8) from CBL
after power-on or new initializing, you have to acknowledge (ON)
after initial processing is completed.
Refer to chapter 4.3 "Initial process and initial data setting"
RY (n+1)9
Initial data setting
request flag
If you want to reset the CBL interface turn ON. The initial data setting
complete (RX(n+1)9 turns ON after resetting is finished.
Refer to chapter 4.3 "Initial process and initial data setting"
RY (n+1)A
Error reset request flag
When the error reset request flag is turned ON, the error status flag
(RX(n+1)A) is turned OFF.
Note: edge sensitive signal (0-1-transition for resetting)
Refer to chapter 4.3 "Initial process and initial data setting"
CC-Link I/O control
and status bits
All manuals and user guides at all-guides.com
Summary of Contents for Simovert Masterdrive FANC-SB
Page 8: ...All manuals and user guides at all guides com ...
Page 14: ...All manuals and user guides at all guides com ...
Page 48: ...All manuals and user guides at all guides com ...
Page 58: ...All manuals and user guides at all guides com ...
Page 70: ...All manuals and user guides at all guides com ...
Page 72: ...All manuals and user guides at all guides com ...