7.1.2
Procedure when commissioning
Commissioning steps
This section shows you how to configure a system and test the configured drives and axes.
The commissioning steps are listed below. The sequence is only an example and can vary
depending on the supplementary conditions.
1. Configure the SINAMICS Integrated:
You can configure the integrated drives (SINAMICS Integrated) offline or online:
– Offline configuration:
Performing D4x5-2 offline configuration (Page 175) and CX32-2 offline configuration
For offline configuration, all of the components and their article numbers must be known.
– Online configuration:
Performing D4x5-2 online configuration (Page 203) and
Performing CX32-2 online configuration (Page 219)
During online configuration, you can download all of the information from the connected
DRIVE‑CLiQ components to your user project.
Note:
The next two sections describe how a SIMOTION D4x5‑2 including SINAMICS
Integrated is configured. The described procedure also applies when CX32‑2 controller
extensions are used.
The Section
Configuring a CX32‑2 also describes the step-by-step commissioning with
a CX32‑2 controller extension. The advantage of a step-by-step configuration is that the
location and cause of an error are easier to identify.
2. Test a drive with the drive control panel (Page 254)
3. Create an axis with the axis wizard (Page 257)
4. Test an axis with the axis control panel (Page 264)
5. Activate the infeed (Line Module) (Page 267)
6. Set up addresses and telegrams (Page 271)
7. Link an additional encoder (optional) (Page 275)
8. Configure drive-related I/Os (with symbolic assignment) (Page 282)
9. Configure the technology (Page 288)
10.Optimize the drive and controller (Page 301)
This section also contains additional configuration information, e.g. for vector drives, Safety
Integrated, etc.
Commissioning (software)
7.1 Overview of commissioning
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B