7.3
Performing an online configuration for the D4x5-2
7.3.1
Overview
Introduction
You can configure the plant in online mode after having completed its wiring. You can load the
data of SINAMICS components connected via DRIVE‑CLiQ to your PG/PC using the
"Automatic configuration" function. However, this is only possible for initial commissioning.
Note
Components without DRIVE-CLiQ connection must be edited in offline mode. You may need
to edit DRIVE-CLiQ components which were detected in the course of automatic configuration
(for example, adding encoder data if using SMC modules).
Requirements
● Your system has been mounted and wired
● You have created a project in SIMOTION SCOUT and inserted a SIMOTION D4x5‑2 in the
project
● You have configured the communication between the SIMOTION D4x5‑2 and the PG/PC.
See Section Creating a project and configuring the communication (Page 124).
Procedure
The online configuration involves the following steps:
● Establish the online connection (Page 203)
● Starting automatic configuration (Page 204)
● Reconfiguring SINAMICS components (Page 209)
● Downloading a project to the SIMOTION D4x5-2 (Page 209)
7.3.2
Establish an online connection
Requirement
You have created a project.
Procedure
This section outlines the procedure for initial commissioning.
Commissioning (software)
7.3 Performing an online configuration for the D4x5-2
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
203