Name
Color
State
Meaning
D4x5-2:
SY/MT
1)
CBE30-2:
SYNC
1)
Green
Off
The PROFINET interface has not synchronized yet to the send cycle clock
of PROFINET IO with IRT, or PROFINET IO with IRT has not been config‐
ured (e.g. only PROFINET IO with RT or TCP/IP communication).
If IRT data has been configured for SIMOTION, the PROFINET interface
generates a local substitute cycle clock as long as there is no synchroni‐
zation to the send cycle clock of PROFINET IO with IRT:
SIMOTION task system has synchronized to the local substitute cycle clock
of the PROFINET interface. SINAMICS Integrated and external isochro‐
nous DP interfaces are synchronized to the local substitute cycle clock of
the PROFINET interface.
On
The PROFINET interface has synchronized to the send cycle clock of
PROFINET IO with IRT.
If isochronous IRT data has been configured for SIMOTION, then the fol‐
lowing applies:
The task system of SIMOTION has synchronized to the send cycle clock
of PROFINET IO with IRT.
SINAMICS Integrated and external isochronous DP interfaces are
synchronized to the send cycle clock of PROFINET IO with IRT.
If no isochronous IRT data has been configured for SIMOTION, this state
indicates that only the PROFINET interface is synchronized to the send
cycle clock of PROFINET IO with IRT. The PROFINET interface is then
used to forward the IRT data.
Flashing
(2 Hz)
The PROFINET interface has synchronized to the send cycle clock of
PROFINET IO with IRT
If IRT data has been configured for SIMOTION, then the following applies:
The task system of SIMOTION has synchronized to the send cycle clock
of PROFINET IO with IRT.
SINAMICS Integrated and external isochronous DP interfaces are not yet
synchronized to the send cycle clock of PROFINET IO with IRT.
1)
If no IRT has been configured, then generally no synchronization will be made to the send cycle clock. LED is off.
Note
If the I‑Device is deactivated via the system function _deactivateDpSlave, the PN or FAULT
LED will respond as if the I‑Device had not been configured.
The PN/FAULT LED is lighted if an IO controller is configured and no IP address exists.
If no IO controller is configured, the LED will not light up.
Diagnostics
9.1 Diagnostics via LED displays
SIMOTION D4x5-2
392
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B