Interfaces
3.7 PROFIBUS DP interfaces
SIMOTION D4x5-2
Manual, 02/2012
67
Interface assignment for X126
Table 3- 17 PROFIBUS DP interface X126
Pin
Signal name
Signal type Meaning
1
--
--
Reserved, do not use
2
M
VO
Ground to P24_SERV
3
1RS_DP
B
RS-485 differential signal
4
1RTS_DP
O
Request to send
5
1M
VO
Ground to 1P5
6
1P5
VO
5 V power supply for bus terminal, external, short-circuit
proof
7
P24_SERV
VO
24 V for teleservice, short-circuit proof, 150 mA maximum
8
1XRS_DP
B
RS-485 differential signal
9
--
--
Reserved, do not use
The 1P5 voltage is provided exclusively for the bus terminal.
No OLPs are permitted.
Signal type: VO = Voltage output (power supply); O = Output; B = Bidirectional
Interface assignment for X136
Table 3- 18 PROFIBUS DP interface X136
Pin
Signal name
Signal type Meaning
1
--
--
Reserved, do not use
2
M
VO
Ground to P24_SERV
3
2RS_DP
B
RS-485 differential signal
4
2RTS_DP
O
Request to send
5
1M
VO
Ground to 1P5
6
1P5
VO
5 V power supply for bus terminal, external, short-circuit
proof
7
P24_SERV
VO
24 V for teleservice, short-circuit proof, 150 mA maximum
8
2XRS_DP
B
RS-485 differential signal
9
--
--
Reserved, do not use
The 1P5 voltage is provided exclusively for the bus terminal.
No OLPs are permitted.
Signal type: VO = Voltage output (power supply); O = Output; B = Bidirectional
Summary of Contents for SIMOTION TB30
Page 10: ...Table of contents SIMOTION D4x5 2 10 Manual 02 2012 ...
Page 36: ...Description 1 9 CompactFlash card SIMOTION D4x5 2 36 Manual 02 2012 ...
Page 46: ...Operator control hardware 2 3 7 segment and LED displays SIMOTION D4x5 2 46 Manual 02 2012 ...
Page 72: ...Interfaces 3 10 USB interfaces SIMOTION D4x5 2 72 Manual 02 2012 ...
Page 134: ...Supplementary system components 6 11 DMC20 DRIVE CLiQ hub SIMOTION D4x5 2 134 Manual 02 2012 ...