Alarm, fault and system messages
11.2 Reporting diagnostics information
SIMATIC MV420 / SIMATIC MV440
Operating Instructions, 04/2013, A5E02371045-06
337
Message
Value
(onboard
PROFINET
diagnostics)
Value
(TCP/IP and
RS232)
Value
(FB45,
error_MOBY)
Value
(Ident
profile,
STATUS
byte)
(byte 0,
byte 1,
byte 2)
Description
How to remedy the
problem
Error
Archiving/
MMI
communication
W#16#500E 14
0C
E1, FE, 01 Error in
communication
over the archiving
connection: There
is no TCP
connection, the
server does not
respond within the
set time limit or
violates the
archiving protocol.
Check the connection to
the server. Make sure
that the data is
processed by the server
in an adequately short
time and that the
protocol is maintained.
Error - lamp
overload
W#16#500F 15
10
E4, FE, 06 The connected
lamp was
overloaded. The
selected or default
"Maximum duty
cycle" from
Options/Lighting
was exceeded.
Reduce the trigger
frequency, reduce the
exposure time or use a
more powerful lamp.
Reserved
program
number error
W#16#5010 16
02
E6, FE, 04 You are attempting
to save program
number 15 via
digital I/O or
PROFINET IO.
This number
cannot be saved
via these
interfaces.
Select a program
number of between 1
and 14 or user another
interface to save
program number 15.
Error -
PROFINET IO
error
W#16#5011 17
-
-
Error in PROFINET
IO communication
Make sure that the
parameters for
communication over
PROFINET IO and the
communication partners
are correctly configured
and active. Check the
connection to the I/O
controller.
Error internal
file error
W#16#5005 05
13
E4, FE, 04 An error occurred
while saving to
read-only memory.
Please contact technical
support if this error
occurs frequently.