Wiring
3.2 Installing position
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
15
3.2
Installing position
Note
When installing and connecting up the CM 1xDALI, refer to the instructions in the system
manual SIMATIC ET 200SP Distributed I/O system
https://support.industry.siemens.com/cs/ww/en/view/58649293
) note the information in the
document "Use of subassemblies/modules in a Zone 2 Hazardous Area" that you will find on
the Internet at the following address:
Link: (
https://support.industry.siemens.com/cs/ww/en/view/78381013
NOTICE
Installation location - Dependency of the temperature range
The upper and lower ventilation slits of CM 1xDALI cannot be covered, allowing adequate
ventilation. Above and below the module, there must be a clearance of 25 mm to allow air
to circulate and prevent overheating.
Installation position
Installation position of the CM 1xDALI
Horizontal installation of the CM 1xDALI
Vertical installation of the CM 1xDALI