Programming
5.7 Configuration function blocks
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
99
Parameter
Declaration Data type Memory
area
Description
CM_DALI
InOut
"DALI_CT
RL"
The data block of DALI_CTRL specifies the CM 1xDALI which
communicates with the current function block.
BUSY
Output
BOOL
I, Q, M, D,
L
Status parameter:
•
BUSY = 0: Processing of job is terminated.
•
BUSY = 1: Job is still being committed.
ACTIVE
BOOL
I, Q, M, D,
L
Status parameter:
•
ACTIVE = 0: Job is not yet started.
•
ACTIVE = 1: Job is being executed.
DONE
BOOL
I, Q, M, D,
L
Status parameter:
•
DONE = 0: Job is not yet started or still executing.
•
DONE = 1: Job is executed without errors.
ERROR
BOOL
I, Q, M, D,
L
Status parameter:
•
ERROR = 0: No error occurs.
•
ERROR = 1: Error occurs during processing.
STATUS
BYTE
I, Q, M, D,
L
When ERROR = 0, STATUS has
following three values:
•
16#00: Idle
•
16#01: Executing
•
16#7F: Completed
When ERROR = 1, STATUS
shows the detailed error code.
For the detailed meaning of each
error code, refer to Parameter
1
For the detailed description of sensor instance type-related parameters for configuring DALI_SENSOR_INST_PARAM,
refer to the following table.
Table 5- 5
Sensor instance type-related parameters for configuring DALI_SENSOR_INST_PARAM
Attributes BYTE Type 1 (push button) Type 2 (absolute input)
Type 3 (occupancy)
Type 4 (light sensor)
Read/Write
0
tShort
Deadtime
Hold time
Hysteresis
1
tDouble
Report time
Report time
Hysteresis min
2
tRepeat
Not used
Deadtime
Report time
3
tStuck
Not used
Deadtime