Installation
28
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
1.3.4 Installation
Position
SICAM CMIC may only be installed horizontally.
horizontal mounting position
vertical mounting position
Note
Not permitted is the vertical installation or installations on the ceiling and on the floor (excessive tempera-
ture, dust load).
1.3.5
DIN Rail (TS35 Rail)
For the installation of SICAM CMIC a DIN rail is to be used, which conforms to the European
Standard EN 50 022. The orientation and position in which the DIN rail is to be installed must
be determined locally.
The DIN rail must be installed horizontally on a vertical wall.
Warning
The connection of the DIN rail with the cabinet/rack must guarantee a reliable grounding of SICAM CMIC.
The cabinet/rack itself must be grounded properly.
F4
F3
F2
F1
P OK
RY
E R
E TH
L K1
P K1
RS-232
OH2
RS-485
OH3
E TH
L K4
P K4
S D
X4
F
4
F
3
F
2
F
1
PO
K
RY
ER
E
TH
LK
1
PK
1
R
S-
23
2
OH
2
R
S-
48
5
OH
3
E
TH
LK
4
PK
4
S
D
X
4
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...