Engineering via SICAM WEB
228
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
5.1.10.2.1 Supported Type Identifications and Possible Values
Type Identification
Possible value
Single-point information
(TI 30)
Off (0)
On (1)
Double-point information
(TI 31)
Intermediate (00),
Off (01)
On (10)
Error (11)
Single command (TI 45)
Off (0)
On (1)
Double command (TI 46)
Terminated (00)
Off (01)
On (10)
Error (11)
Tap position command (TI 47)
Terminated (00)
Lower (01)
Higher (10)
Error (11)
Counter value (TI 37)
Measured value normalized
(TI 34)
-1…+1
Measured value scaled (TI 35)
-32768…+32767 (15 Bit + sign)
Measured value short floating
point (TI 36)
-1.000•10
15
…+1.000•10
15
Setpoint normalized (TI 48)
-1…+1
Setpoint scaled (TI 49)
-32768…+32767 (15 Bit + sign)
Setpoint short floating point
(TI 50)
-1.000•10
15
…+1.000•10
15
Value from device without conversion
The values are converted depending on the type identification (TI). Analog values are dis-
played as conditioned values.
The data format of the displayed inputs corresponds to the setting of the respective data point
on the I/O module (signal list).
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...