Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC
193
DC8-001-2.09, Edition 08.2016
Processing type
Parameter
Meaning
Sync_Input_t_1
Within this time (in sec) the enabling over the
syncronisation input must occur on the com-
mand.
0 = no syncronisation over syncronisation in-
put.
Attention: Function only active if sync_t = 0
0.1 to 6553.5
1_out_of_n_t_1
Within this time (in sec) the 1 out of n enabling
must occur on the command.
0 = no 1 out of n enabling necessary.
Attention: Function only active if sync_t = 0.
0.1 to 25.5
Sw_Seq_command_seq_0
Switching sequence: output additional com-
mand before or after the command
Sw_Seq_addtl_com_0
Switching sequence: Select the additional
command
Sw_Seq_command_seq_1
Switching sequence: output additional com-
mand before or after the command
Sw_Seq_addtl_com_1
Switching sequence: Select the additional
command
RS_Mon_Source_0
Source of state information for state infor-
mation monitoring
•
Peripherals
•
open-/closed loop control function
•
both (logical OR)
RS_Mon_Source_1
Source of state information for state infor-
mation monitoring
•
Peripherals
•
open-/closed loop control function
•
both (logical OR)
SID-BSE
Source identification basic system element
SID-ST
Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
SID-SSE
Source identification supplementary system
element
QOC>8
If QOC > 8 (Qualifier of Command) is accept-
ed, so all QOC > 8 will be interpreted as
QOC = 0
ON_before_OFF
Definition of the order for the wiring of double
commands/double point information.
•
NO: OFF is I/O with lower I/O number ON is
I/O with higher I/O number.
•
YES: ON is I/O with lower I/O number OFF
is I/O with higher I/O number
Regulating_command
Use as regulating command (S)
NO/YES
RS_Image
Parameter works only with ACP 1703 platform
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...