Engineering via SICAM WEB
232
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
Example: single-point information output
•
In the directory tree, mark the corresponding DO module
•
Click on the side bar left beside the status area, if you want to extend it
•
Mark the row with the desired datapoint
Control area:
•
Select a “New value”
•
Click on the button
The new process value is transferred to the target device and displayed in the column
Value
.
Type Identifications and Possible Values
The following type identifications and attributes are supported to force a new process value:
Type identification
New value
Select
before
execute
Qualifier of command
Origi-
nator
Single-point information
(TI 30)
Off (0)
On (1)
Single command (TI 45)
Off (0)
On (1)
No
Yes
No determination
Long command execution time
Short command execution time
Persistent command
0…255
Double command (TI 46)
Off (01)
On (10)
Tap position command
(TI 47)
Lower (01)
Higher (10)
Measured value normal-
ized (TI 34)
-1…+1
Measured value scaled
(TI 35)
-32768…
+32767
Measured value short
floating point (TI 36)
-1.000•10
15
…
+1.000•10
15
Setpoint command nor-
malized (TI 48)
-1…+1
No
Yes
Setpoint command scaled
(TI 49)
-32768…
+32767
Setpoint command short
floating point (TI 50)
-1.000•10
15
…
+1.000•10
15
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...