Engineering via SICAM WEB
154
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
5.1.5
Configuring
Time
Management
•
Menu
Home | Settings
5.1.5.1 Time Synchronization
The internal clock of SICAM CMIC serves for the time tagging of generated data
•
from the periphery
•
from the optional
Open/closed-loop control function
•
for the records in the diagnosis
The resolution of the time tag is 1 ms.
The settings for the time synchronization reside in the directory tree under
SICAM CMIC | Master module | Time management | Common settings
(the checkbox
Show all parameters
must be activated).
SICAM CMIC supports the following time synchronization variants (selectable with parameter
Synchronizing of the automation unit
):
•
Remote synchronization via serial communication or via LAN
•
Free running
With the Parameter
Monitoring time for synchroniz. event
the monitoring fort he re-
mote synchronization is defined. If the time was already set and if there is no synchronization
within the parameterized time, a warning is recorded in the diagnosis.
With the Parameter
Unit of time for free running and monitoring time
the unit of
the monitoring time is defined (seconds or minutes).
You find the detailed information on the time synchronization reside in the manual
SICAM
RTUs Common Functions System and Basic System Elements, chapter "System Services",
section "Time Management", section "Time Synchronization"
.
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...