Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC
231
DC8-001-2.09, Edition 08.2016
Example: Setpoint command, normalized
•
In the directory tree, mark the corresponding AO module
•
Click on the side bar left beside the status area, if you want to extend it
•
Mark the row with the desired datapoint
Control area:
•
Select a “New value”
The data format corresponds to the setting of the data point on the I/O module (signal list).
•
Select the “Select before execute“ option
With selection
Yes
and button you activate the select command. You activate the ex-
ecute command, when you click on the button once more within the adjusted time
(
select_execute_t
).
With selection
No
and button you activate the execute command directly.
The new process value is transferred to the target device and displayed in the column
Value
.
You find further details in the manual
SICAM RTUs Common Functions Peripheral Elements
According to IEC 60870-5-101/104,
chapter
"Setpoint Values by means of Currents and Volt-
ages", section "Select and Execute Command"
.
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...