Preparing the Engineering
SICAM RTUs, User Manual SICAM CMIC
81
DC8-001-2.09, Edition 08.2016
3.7.2.2 Communication with the Target Device
For the parameterization the target device must be connected with the engineering PC and
switched on. In the master control module of the target device a SD card must be equipped.
The establishing of a communication connection between engineering PC and the target
device takes place via adjustable IP addresses. For the initial parameter setting of
SICAM CMIC, default IP addresses are available. These are specific for the respective physi-
cal connection.
With local engineering, fixed IP addresses are used since they are required only temporarily
for the parameterization of the target device.
Default IP Configuration in SICAM CMIC
Parameter
Value
Meaning/Remark
<Own IP address>
172.16.0.1
Address of SICAM CMIC web server via serial
interface X2 (fixed)
Autoconfiguration
NO
Configuration via DHCP service deactivated
Mode of the Ether-
net ports
1 IP address (con-
nected ports in switch
mode)
Common IP address ON Ethernet interfaces X1
and X4
Parameter “Mode of
the Ethernet ports”
display (selection)
Mode for X1 and X4 can be selected (configura-
tion of separate IP addresses enabled)
Own IP address
172.16.0.3
Address of SICAM CMIC web server via Ether-
net interface X1 and X4
Subnet mask
255.255.255.0
0.0.0.0 = not used
Default gateway
0.0.0.0
0.0.0.0 = not used
In practice the default gateway is assigned on
the smallest (193) or greatest (222) usable IP
address in the network.
If the own network is connected via a router, the
address of the router is to be set.
Network connection
LAN
Utilized transmission media
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...