Engineering via SICAM TOOLBOX II
SICAM RTUs, User Manual SICAM CMIC
119
DC8-001-2.09, Edition 08.2016
4.1.9.3.2 Simulation Of Spontaneous Data Points
With the tool "Message Simulation" messages can be transmitted from the SICAM TOOLBOX
II to automation units. Just one message or up to 100 messages in succession can be trans-
mitted; in addition sequential delays and message repetitions can be defined.
The messages can be passed in at defined points of the system. With this function the follow-
ing possibilities exist:
•
Setting of outputs
•
Simulation of the communication from and to protocol elements
•
Data traffic from and to the application program
•
Data traffic from and to special functions (for example set counters, set time)
Pay attention that due to the simulation the plant state can change.
Warning
The manual controlling of outputs with the plant running can lead to damage to persons and machines.
Ensure that aggregates in the control area of the command output and those subsequent aggregates in
the process chain are protected and that persons in the vicinity are warned.
You find the instruction for this test function in the
SICAM TOOLBOX II Online Help, chapter
"Service Programs“, section "Message Simulation"
.
You find further information in the manual
SICAM RTUs Common Functions System and
Basic System Elements, chapter "System Services", section "Message Simulation"
.
4.1.9.3.3 Check The Connection To Automation Units
The tool "Topology Test" is used for the acquisition of all automation units in a SICAM RTUs
automation network that are reachable or non-reachable from the automation unit momentarily
physically connected.
You find the instruction for this test function in the
SICAM TOOLBOX II Online Help, chapter
"Service Programs“, section “Service Programs”section "Topology Test"
.
Summary of Contents for SICAM CMIC
Page 8: ...Preface 8 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 46: ...Installation 46 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 62: ...Interfaces and Circuitry 62 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 102: ...Preparing the Engineering 102 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 334: ...Error Handling 334 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 404: ...Use Cases 404 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 ...
Page 414: ...Glossary 414 SICAM RTUs User Manual SICAM CMIC DC8 001 2 09 Edition 08 2016 X Z ...